Active harmonic filter and power optimizer, PQSine S series (B44066F*S) · EPCOS AG / TDK Electronics

PQSine S is an active harmonic filter: it measures the load current continuously, works out which harmonics it contains, and injects a current in anti-phase so that what the network sees is close to a clean sine wave. Because it corrects what it measures rather than switching fixed steps, it does not care how many non-linear loads there are or how the spectrum shifts through the day, which is precisely where passive filters run out of answers. The same unit also compensates fundamental reactive power, inductive and capacitive, balances the load between phases, and in a four-wire configuration takes the current out of the neutral conductor. Harmonics are corrected up to the 51st order, individually selectable and adjustable, with an attenuation rate above 97 %.

Key Features

  • 01Harmonic compensation up to the 51st order, individually selectable and adjustable between 0 and 100 %
  • 02Harmonic attenuation rate > 97 % for the signature harmonic spectrum
  • 03Reactive power compensation (inductive and capacitive) and load balancing between phases, including neutral current compensation on 4-wire systems
  • 04Very fast: reaction time approx. 50 µs, overall response time < 15 ms
  • 05Three-level IGBT topology, 20 kHz switching frequency, advanced FFT control
  • 06Rack, wall and floor mounting; wall units with a built-in 4.3 inch HMI touch display
  • 07Modbus over RS485 and TCP/IP over Ethernet (RJ45) for interconnection and monitoring
  • 08Comprehensive protection: overload, short-circuit, over-temperature, over/undervoltage, converter bridge reverse, resonance, fan fault

Applications

Technical Specifications

PQSine S

Technical Specifications · PQSine S
Series / ordering codePQSine S, B44066F*S (individual types per the datasheet tables)
Rated voltage and range200 V (173 … 263 V) · 400 V (228 … 456 V) · 480 V (384 … 552 V) · 600 V (420 … 690 V) · 690 V (483 … 793 V)
Mains frequency50 / 60 Hz (range 45 … 62 Hz)
Network configuration3P3W / 3P4W
Individual module capacity25 / 35 / 50 / 60 / 75 / 100 / 150 A at 200 and 400 V; 50 / 75 / 90 / 100 A at 480, 600 and 690 V. Up to 600 A per floor-mounted panel at 200 / 400 V, and 1200 A in the double-width cabinet
Rated compensation current of neutral line75 / 105 / 150 / 180 / 225 / 300 / 450 A
Filtering range2nd … 51st harmonic, individually selectable, magnitude adjustable 0 … 100 %
Harmonic attenuation rate> 97 % for the signature harmonic spectrum
Reaction time / overall response timeApprox. 50 µs / < 15 ms
Target power factorAdjustable between −1 and +1
TopologyThree-level IGBT
Switching frequency20 kHz
Overall efficiency97 % at 100 % load; typical power losses < 3 %
CT ratio setting150/5 … 10000/5
CommunicationRS485 and network interface (RJ45); Modbus and TCP/IP
DisplayWall-mounted: built-in 4.3 inch HMI. Rack-mounted: no built-in display, external 7 inch HMI required. Floor-mounted: centralized 7 inch HMI
Displayed parametersGrid and load side simultaneously: voltage, current, power factor, ITHD %, VTHD %, active/reactive/apparent power; AHF compensation current in A and %
MountingRack, wall and floor mounting
Net weight (wall / rack module)18 / 18 / 23 / 35 / 44 kg by rating
Noise level< 56 dB up to 100 A; < 65 dB at 150 A
Operating temperature−10 … +40 °C; higher temperatures with derating
Relative humidity95 %, non-condensing
Protection classIP20; other IP classes available on request
Altitude1500 m; between 1500 and 4000 m power derated by 1 % per additional 100 m
Certification / standardsCE and IEEE 61000; ETL (UL 508, CSA C22.2 # 2014) on the 480, 600 and 690 V ranges. Compliance with IEEE 519 and ER G5/4