Skip to content
UMG 96RM-E · Janitza Electronics GmbH
Janitza Electronics GmbHEnergy Analyzers

UMG 96RM-E

Panel-mount analyzer with Ethernet + RCM

The UMG 96RM-E pairs the standard 96RM measurement engine with built-in Ethernet and residual-current monitoring, making it one of the more network-ready and safety-oriented members of the family. It works as a straightforward IP-connected meter (Modbus TCP/IP, BACnet/IP, or Modbus gateway for downstream RS485 devices like the UMG 103-CBM) and as an early-warning tool for insulation faults via its dedicated RCM inputs.

Key Features

  • 01Built-in Ethernet (RJ45) alongside RS485; can act as a Modbus Gateway
  • 02BACnet/IP support in addition to Modbus RTU/TCP
  • 03Built-in web server with waveform display, accessible from a browser
  • 042 residual current monitoring channels for insulation-fault detection
  • 05256 MB data memory (~10,000,000 values)
  • 06Harmonics to the 40th order

Applications

Technical Specifications

UMG 96RM-E

Technical Specifications · UMG 96RM-E
Measurement inputs4 voltage channels (0–300V L-N, 0–520V L-L); current I1-I4 rated 5A; residual current I5/I6 rated 30 mA RMS
Accuracy classV/I Class 0.2; active energy Class 0.5S; residual current Class 1.0 (IEC 61557-12)
Communication protocolsRS485 (Modbus RTU); Ethernet (TCP/IP, DHCP, Modbus/TCP, NTP, FTP, SNMP); Modbus Gateway; BACnet/IP
DisplayBacklit LCD, 2-key operation; web server with waveform views
Memory / data logging256 MB (~10,000,000 stored values)
Installation typePanel mount, cut-out 92×92 mm, depth ~104–110.5 mm, ~370 g
Harmonics1st–40th (V and I to 2.5 kHz), THD, power factor, flicker, transients
Residual current monitoring (RCM)2 RCM inputs, rated 30 mA RMS, Type A/B per IEC/TR 60755, 1 µA resolution
Certifications / standardsUL listed; EN 50160/ISO 50001; IP40/IP20/IP54; Made in Germany
Power supply230 V option 90–277 V AC / 90–250 V DC (max 7.5 VA); 24 V option 24–90 V AC/DC (max 7.5 VA)

Technical values are taken from the manufacturer's published documentation. Confirm against the current datasheet before ordering.

Downloads

Datasheets, manuals and technical documentation are available from the manufacturer's document centre, or on request from us.

Get in Touch

Contact us about this product

Let us work out the right model for your application. Share your single-line diagram or measurement data and our technical team will review it.