UMG 96RM
Panel-mount multifunctional analyzer (base model)
The UMG 96RM is the baseline model of Janitza's flagship 96 mm panel-mount analyzer family, used to measure and monitor electrical parameters across low- and medium-voltage distribution systems. It's typically deployed to record load profiles for ISO 50001 energy management, break down consumption for cost-center billing, and act as a Modbus data source for BMS/PLC systems. The rest of the family (-P, -M, -E, -CBM, -PN) builds on this same hardware with added communication/I/O options.
Key Features
- 012-key operation with backlit LCD display
- 02Harmonics to the 40th order, rotating-field-component detection
- 03Up to 14 tariffs depending on variant; 4-quadrant energy measurement
- 042 digital/pulse outputs
- 05RS485/Modbus RTU standard interface
- 06Base platform for 5 expanded variants (-P, -M, -E, -CBM, -PN)
Applications
- Power Quality SolutionsPower quality problems such as harmonics, voltage sags and swells, flicker, transients and voltage unbalance can occur in electrical systems. They can arise from non-linear loads, sudden load changes, network events and the electrical structure of the facility itself. Poor power quality can cause overheating in equipment, nuisance tripping, energy losses, shorter equipment life and interruptions to production continuity. At EPKOM we use power quality analyzers to measure and monitor LV and MV systems, recording harmonics, voltage events and the other power quality parameters. We evaluate the resulting data against the relevant standards, such as EN 50160, IEC 61000 and IEEE 519, according to the measurement point and the scope of the application. Following measurement and analysis, we apply active and passive harmonic filters, SVG systems, compensation solutions and power quality monitoring systems according to the needs of the facility, helping the electrical infrastructure run more safely, efficiently and stably.
- Energy Monitoring SystemsEnergy monitoring systems measure and analyse electricity consumption continuously, at facility, feeder, department or machine level. Alongside electricity, other energy sources such as water, natural gas and compressed air can be tracked through the same system. Data from Janitza energy analyzers is collected centrally in the GridVis software, where consumption trends, load profiles and energy performance indicators can be followed. Automatic reporting and alarm functions make abnormal consumption and energy losses quick to identify. Energy monitoring systems help to allocate energy costs correctly, to identify inefficient points of consumption and to improve energy performance continuously. They also support ISO 50001 energy management processes and make it possible to track energy performance indicators such as PUE in data centers.
Technical Specifications
UMG 96RM
| Measurement inputs | 4 voltage channels (L-N to 300 V, L-L to 520 V); current rated 5 A (0–6 A RMS) |
|---|---|
| Accuracy class | P Class 0.5, Q Class 1, S Class 0.5, active energy Class 0.5/0.5S, V/I Class 0.2, frequency Class 0.05 (IEC 61557-12) |
| Communication protocols | RS485, Modbus RTU/slave, 9.6–115.2 kbps |
| Display | Backlit LCD, 2-key operation |
| Memory / data logging | Large measured-data memory (capacity not published for base model; 256 MB on variants) |
| Installation type | Panel mount, cut-out 92×92 mm, ~97×100×42 mm, ~265 g |
| Harmonics | 1st–40th (V and I), THD Class 1.0 |
| Residual current monitoring (RCM) | Not available on the base model (added on -E and -PN) |
| Certifications / standards | 300 V CAT III (voltage) / CAT II (current); IP40/IP20/IP54; pollution degree 2 |
| Power supply | 230 V option 90–277 V AC/DC (max 7.5 VA); 24 V option 24–90 V AC/DC (max 3.5 VA) |
Technical values are taken from the manufacturer's published documentation. Confirm against the current datasheet before ordering.
Downloads
Datasheets, manuals and technical documentation are available from the manufacturer's document centre, or on request from us.
Get in Touch
Contact us about this product
Let us work out the right model for your application. Share your single-line diagram or measurement data and our technical team will review it.