
UMG 96-PA
Modular panel-mount power analyzer
The UMG 96-PA is a compact 96×96 mm panel-mount meter that tracks voltage, current, power, and energy across a facility's distribution network. Its modular architecture lets a customer start with a basic metering unit and later add plug-in modules; such as residual/differential current monitoring, neutral-conductor measurement, or an Ethernet/Modbus gateway, so the same physical device can be upgraded in the field.
Key Features
- 01Modular, plug-and-play expansion modules (retrofit-capable)
- 02Color graphic display, 6-button navigation
- 03Harmonics to the 40th order
- 04Built-in web server accessible from browser/mobile
- 05Compatible with GridVis® software
- 06600 V CAT III rated
Applications
- Power Quality SolutionsPower quality problems such as harmonics, voltage sags and swells, flicker, transients and voltage unbalance can occur in electrical systems. They can arise from non-linear loads, sudden load changes, network events and the electrical structure of the facility itself. Poor power quality can cause overheating in equipment, nuisance tripping, energy losses, shorter equipment life and interruptions to production continuity. At EPKOM we use power quality analyzers to measure and monitor LV and MV systems, recording harmonics, voltage events and the other power quality parameters. We evaluate the resulting data against the relevant standards, such as EN 50160, IEC 61000 and IEEE 519, according to the measurement point and the scope of the application. Following measurement and analysis, we apply active and passive harmonic filters, SVG systems, compensation solutions and power quality monitoring systems according to the needs of the facility, helping the electrical infrastructure run more safely, efficiently and stably.
- Energy Monitoring SystemsEnergy monitoring systems measure and analyse electricity consumption continuously, at facility, feeder, department or machine level. Alongside electricity, other energy sources such as water, natural gas and compressed air can be tracked through the same system. Data from Janitza energy analyzers is collected centrally in the GridVis software, where consumption trends, load profiles and energy performance indicators can be followed. Automatic reporting and alarm functions make abnormal consumption and energy losses quick to identify. Energy monitoring systems help to allocate energy costs correctly, to identify inefficient points of consumption and to improve energy performance continuously. They also support ISO 50001 energy management processes and make it possible to track energy performance indicators such as PUE in data centers.
Technical Specifications
UMG 96-PA
| Voltage inputs | 3P4W up to 417/720V, 3P3W up to 600V, 1-phase up to 480V; range 0.01–600 Vrms (L-N) |
|---|---|
| Current inputs | Rated 5A, range 0.005–6 Arms, overload 60A/1s |
| Accuracy | Power/energy Class 0.2S (…/5A) or 0.5 (…/1A); V/I Class 0.2 (IEC 61557-12) |
| Harmonics | 1st–40th order; flicker, dips/swells, transients, imbalance, THD |
| Digital I/O | 3 digital inputs, 3 digital/pulse outputs; optional 0–20 mA analog output |
| Communication protocols | RS485 (Modbus RTU); optional Ethernet module adds Modbus TCP/IP + Gateway |
| Memory / data logging | 8 MB internal logging |
| Installation type | Panel mount, cut-out 92×92 mm, depth 96 mm |
| Certifications / standards | IP40/IP20/IP54; IK07; UL, ANSI listed |
Technical values are taken from the manufacturer's published documentation. Confirm against the current datasheet before ordering.
Downloads
Datasheets, manuals and technical documentation are available from the manufacturer's document centre, or on request from us.
Get in Touch
Contact us about this product
Let us work out the right model for your application. Share your single-line diagram or measurement data and our technical team will review it.


