Ecosine Evo & Ecosine Max
Passive harmonic filters, Ecosine Evo (FN 3440 / FN 3441) and Ecosine Max (FN 3472 / FN 3481) · TE Connectivity / Schaffner
Passive harmonic filters that bring the distorted current drawn by 6-pulse rectifiers and motor drives back towards a sine wave — the direct route to the limits in IEEE 519. Ecosine Evo covers 1.1 to 250 kW at 400 V / 50 Hz with 5 % THDi at rated power (FN 3440, FN 3441); Ecosine Max is an open panel design for cabinet integration from 209 to 560 kW (FN 3472, FN 3481). Both are plug-and-play: nothing to commission, no switching losses and no parts that wear.
Key Features
- 01Ecosine Evo: 400 V / 50 Hz, 1.1 … 250 kW motor drive rating, 5 % THDi at rated power
- 02Ecosine Max FN 3472: 400 V / 60 Hz, 209 … 358 kW (280 … 480 HP), < 5 % THDi without a DC-link choke
- 03Ecosine Max FN 3481: 480 V / 50 Hz, 315 … 560 kW, < 8 % THDi without and < 5 % THDi with a 4 % DC-link choke
- 04Total demand distortion to IEEE 519; dedicated versions for drives with and without DC-link choke
- 05Best-in-class partial load performance — minimal capacitive current at light load
- 06Overload capability 1.6 × rated current for 1 minute, once per hour
- 07Efficiency > 98 % (Ecosine Evo) and > 99 % (Ecosine Max) at rated voltage and power
- 08MTBF above 200 000 hours; SCCR 100 kA; earthing systems TN, TT and IT
- 09Plug and play, ready to use: no switching losses and no active components to commission
- 10IP 00 and IP 20 enclosures with wall mounting (evo); compact open panel design for cabinet integration (max)
Applications
- Low Voltage Reactive Power Compensation SolutionsIn industrial and commercial facilities the reactive power balance can be upset both by inductive loads such as motors and transformers and by loads with a capacitive effect such as UPS systems, drives and long cable runs. This can disturb the reactive power balance, move the power factor away from the desired level, draw unnecessary current from the network, increase losses and incur reactive energy charges. Low voltage compensation systems hold the power factor at the desired level by providing compensation matched to the facility's inductive or capacitive reactive power demand. Where load changes are rapid, thyristor-switched systems are used to respond quickly to reactive power variation. In facilities where harmonics are present, compensation systems with harmonic filter reactors are applied to keep the capacitors from entering resonance with the network. A correctly engineered compensation system helps to avoid reactive energy charges, to use transformer and cable capacity more effectively, to reduce electrical losses and to improve system performance.
- Harmonic Filter SolutionsNonlinear loads such as frequency converters, rectifiers, UPS systems, power electronics equipment and arc furnaces can cause current and voltage harmonics on the network. High harmonic levels lead to overheating in transformers, cables and capacitors, to increased energy losses, to a risk of resonance and to unexpected failures in sensitive equipment. Harmonics are reduced with active or passive harmonic filter solutions selected according to the facility's load structure and harmonic spectrum. Passive harmonic filters are effective at reducing specific harmonic components, while active harmonic filters compensate harmonics in real time under variable load conditions, providing dynamic filtering. At EPKOM we determine the filter type and capacity that suits the facility from power quality measurements and harmonic analysis, and engineer our solutions taking IEEE 519 and the relevant IEC/EN standards into account. This reduces harmonic levels, protects equipment and allows the electrical system to run more safely and efficiently.
Technical Specifications
Ecosine Evo & Ecosine Max
| Series | Ecosine Evo FN 3440 and FN 3441; Ecosine Max FN 3472 and FN 3481 |
|---|---|
| Nominal operating voltage | Ecosine Evo FN 3440 / FN 3441: 3 × 380 … 415 V AC ±10 %. Ecosine Max FN 3472: 3 × 380 … 415 V AC ±10 %. Ecosine Max FN 3481: 3 × 440 … 480 V AC ±10 % |
| Operating frequency | 50 Hz ±1 Hz (FN 3440, FN 3441, FN 3481); 60 Hz ±1 Hz (FN 3472) |
| Nominal motor drive power rating | FN 3440 / FN 3441: 1.1 … 250 kW. FN 3472: 209 … 358 kW (280 … 480 HP). FN 3481: 315 … 560 kW |
| Rated filter input current | FN 3440: 1.63 … 376 A. FN 3441: 1.62 … 376 A. FN 3472: 327 … 563 A. FN 3481: 393 … 709 A |
| Motor drive input current without filter | FN 3440: 3.0 … 530 A. FN 3441: 1.7 … 392 A. FN 3472: 472 … 773 A. FN 3481: 564 … 947 A |
| Total harmonic current distortion THDi | FN 3440 / FN 3441: 5 % at rated power. FN 3472: < 5 % at rated power for drives without Ldc, approx. 3.5 % with a 4 % Ldc. FN 3481: < 8 % without Ldc, < 5 % with a 4 % Ldc. System requirements: THDv < 2 %, line voltage unbalance < 1 % |
| Total demand distortion TDD | According to IEEE 519 |
| Overload capability | 1.6 × rated current for 1 minute, once per hour |
| Efficiency | > 98 % (Ecosine Evo) and > 99 % (Ecosine Max) at rated voltage and power |
| Typical power losses at 40 °C | FN 3440: 61 … 1746 W. FN 3441: 53 … 1398 W. FN 3472: 2832 … 4173 W. FN 3481: 2223 … 3256 W |
| High potential test voltage | P → E 2160 V AC, 1 s (Ecosine Evo); P → E 2520 V AC, 1 s (Ecosine Max) |
| Earthing system | TN, TT, IT |
| Overvoltage category | OV III (IEC 60664-1 / UL 61800-5-1) |
| Temperature range | Ecosine Evo: −25 … +45 °C fully operational, +45 … +70 °C derated. Ecosine Max: −25 … +40 °C fully operational, +40 … +70 °C derated. Transport and storage −25 … +85 °C |
| Cooling | Ecosine Evo: internal fan cooling or external cooling. Ecosine Max: external cooling, min. 1069 m³/h inlet air per frame |
| Protection category | IP 00 and IP 20 (Ecosine Evo); IP 00 open panel, optional IP 20 enclosure (Ecosine Max) |
| SCCR | 100 kA (UL approved on Ecosine Max; external UL-rated fuses required) |
| MTBF (Mil-HB-217F) | > 200 000 h at 40 … 45 °C and rated voltage |
| Weight | FN 3440: 7 … 324 kg. FN 3441: 6 … 246 kg. FN 3472: 245 … 385 kg. FN 3481: 250 … 385 kg |
| Configurations | E0XXSXX with trap disconnect switch, E0XXJXX with trap disconnect jumper; Ecosine Max also available with a circuit breaker module (200 … 400 A) |
| Flammability / design standards | UL 94 V-2; filter to UL 61800-5-1 and EN 61800-5-1; chokes to EN 61558-2-20 or EN 60076-6 |
| Typical applications | Equipment with a front-end six-pulse rectifier, motor drives, factory automation, water and wastewater treatment, fan and pump applications, HVAC installations, mission-critical processes, DC fast chargers |
Technical values are taken from the manufacturer's published documentation. Confirm against the current datasheet before ordering.
Downloads
Datasheets, manuals and technical documentation are available from the manufacturer's document centre, or on request from us.
Technical sources
- www.te.com/en/plp/passive-harmonic-filters/Y45E0.html
- www.te.com/commerce/DocumentDelivery/DDEController?Action=srchrtrv&DocNm=FN3472&DocType=Data%20Sheet&DocLang=English&DocFormat=pdf&PartCntxt=CAT-PA8-F3470
- www.te.com/commerce/DocumentDelivery/DDEController?Action=srchrtrv&DocNm=FN3481&DocType=Data%20Sheet&DocLang=English&DocFormat=pdf&PartCntxt=CAT-PA8-F3480
- www.schaffner.com/product/fn3440
Get in Touch
Contact us about this product
Let us work out the right model for your application. Share your single-line diagram or measurement data and our technical team will review it.