Skip to content
Ecosine Evo & Ecosine Max · TE Connectivity / Schaffner
TE Connectivity / SchaffnerPassive Harmonic Filters

Ecosine Evo & Ecosine Max

Passive harmonic filters, Ecosine Evo (FN 3440 / FN 3441) and Ecosine Max (FN 3472 / FN 3481) · TE Connectivity / Schaffner

Passive harmonic filters that bring the distorted current drawn by 6-pulse rectifiers and motor drives back towards a sine wave — the direct route to the limits in IEEE 519. Ecosine Evo covers 1.1 to 250 kW at 400 V / 50 Hz with 5 % THDi at rated power (FN 3440, FN 3441); Ecosine Max is an open panel design for cabinet integration from 209 to 560 kW (FN 3472, FN 3481). Both are plug-and-play: nothing to commission, no switching losses and no parts that wear.

Key Features

  • 01Ecosine Evo: 400 V / 50 Hz, 1.1 … 250 kW motor drive rating, 5 % THDi at rated power
  • 02Ecosine Max FN 3472: 400 V / 60 Hz, 209 … 358 kW (280 … 480 HP), < 5 % THDi without a DC-link choke
  • 03Ecosine Max FN 3481: 480 V / 50 Hz, 315 … 560 kW, < 8 % THDi without and < 5 % THDi with a 4 % DC-link choke
  • 04Total demand distortion to IEEE 519; dedicated versions for drives with and without DC-link choke
  • 05Best-in-class partial load performance — minimal capacitive current at light load
  • 06Overload capability 1.6 × rated current for 1 minute, once per hour
  • 07Efficiency > 98 % (Ecosine Evo) and > 99 % (Ecosine Max) at rated voltage and power
  • 08MTBF above 200 000 hours; SCCR 100 kA; earthing systems TN, TT and IT
  • 09Plug and play, ready to use: no switching losses and no active components to commission
  • 10IP 00 and IP 20 enclosures with wall mounting (evo); compact open panel design for cabinet integration (max)

Applications

Technical Specifications

Ecosine Evo & Ecosine Max

Technical Specifications · Ecosine Evo & Ecosine Max
SeriesEcosine Evo FN 3440 and FN 3441; Ecosine Max FN 3472 and FN 3481
Nominal operating voltageEcosine Evo FN 3440 / FN 3441: 3 × 380 … 415 V AC ±10 %. Ecosine Max FN 3472: 3 × 380 … 415 V AC ±10 %. Ecosine Max FN 3481: 3 × 440 … 480 V AC ±10 %
Operating frequency50 Hz ±1 Hz (FN 3440, FN 3441, FN 3481); 60 Hz ±1 Hz (FN 3472)
Nominal motor drive power ratingFN 3440 / FN 3441: 1.1 … 250 kW. FN 3472: 209 … 358 kW (280 … 480 HP). FN 3481: 315 … 560 kW
Rated filter input currentFN 3440: 1.63 … 376 A. FN 3441: 1.62 … 376 A. FN 3472: 327 … 563 A. FN 3481: 393 … 709 A
Motor drive input current without filterFN 3440: 3.0 … 530 A. FN 3441: 1.7 … 392 A. FN 3472: 472 … 773 A. FN 3481: 564 … 947 A
Total harmonic current distortion THDiFN 3440 / FN 3441: 5 % at rated power. FN 3472: < 5 % at rated power for drives without Ldc, approx. 3.5 % with a 4 % Ldc. FN 3481: < 8 % without Ldc, < 5 % with a 4 % Ldc. System requirements: THDv < 2 %, line voltage unbalance < 1 %
Total demand distortion TDDAccording to IEEE 519
Overload capability1.6 × rated current for 1 minute, once per hour
Efficiency> 98 % (Ecosine Evo) and > 99 % (Ecosine Max) at rated voltage and power
Typical power losses at 40 °CFN 3440: 61 … 1746 W. FN 3441: 53 … 1398 W. FN 3472: 2832 … 4173 W. FN 3481: 2223 … 3256 W
High potential test voltageP → E 2160 V AC, 1 s (Ecosine Evo); P → E 2520 V AC, 1 s (Ecosine Max)
Earthing systemTN, TT, IT
Overvoltage categoryOV III (IEC 60664-1 / UL 61800-5-1)
Temperature rangeEcosine Evo: −25 … +45 °C fully operational, +45 … +70 °C derated. Ecosine Max: −25 … +40 °C fully operational, +40 … +70 °C derated. Transport and storage −25 … +85 °C
CoolingEcosine Evo: internal fan cooling or external cooling. Ecosine Max: external cooling, min. 1069 m³/h inlet air per frame
Protection categoryIP 00 and IP 20 (Ecosine Evo); IP 00 open panel, optional IP 20 enclosure (Ecosine Max)
SCCR100 kA (UL approved on Ecosine Max; external UL-rated fuses required)
MTBF (Mil-HB-217F)> 200 000 h at 40 … 45 °C and rated voltage
WeightFN 3440: 7 … 324 kg. FN 3441: 6 … 246 kg. FN 3472: 245 … 385 kg. FN 3481: 250 … 385 kg
ConfigurationsE0XXSXX with trap disconnect switch, E0XXJXX with trap disconnect jumper; Ecosine Max also available with a circuit breaker module (200 … 400 A)
Flammability / design standardsUL 94 V-2; filter to UL 61800-5-1 and EN 61800-5-1; chokes to EN 61558-2-20 or EN 60076-6
Typical applicationsEquipment with a front-end six-pulse rectifier, motor drives, factory automation, water and wastewater treatment, fan and pump applications, HVAC installations, mission-critical processes, DC fast chargers

Technical values are taken from the manufacturer's published documentation. Confirm against the current datasheet before ordering.

Get in Touch

Contact us about this product

Let us work out the right model for your application. Share your single-line diagram or measurement data and our technical team will review it.