UMG 96-PA-MID+
MID-certified billing meter (modular)
This is the billing-grade version of the UMG 96-PA panel meter, certified under EU Measuring Instruments Directive (MID) 2014/32/EU so its energy readings can be used for invoicing (tenant sub-billing, feed-in tariffs, inter-department cost allocation). It keeps the same modular hardware as the standard 96-PA but adds tamper-evident sealing, a logbook of any changes to legally relevant parameters, and 2 years of stored meter-reading data for legal metrology audits.
Key Features
- 01MID certification to 2014/32/EU, VDE-tested
- 02Self-contained legal metering: no external tamper-proof chain required
- 03Password protection + physical terminal covers for lead-sealing
- 04Logbook logging changes to legally relevant variables
- 05Stores meter-reading data for 2 years internally
- 06Can act as gateway for up to 30 simple MID sub-meters via Ethernet module
Applications
- Power Quality SolutionsPower quality problems such as harmonics, voltage sags and swells, flicker, transients and voltage unbalance can occur in electrical systems. They can arise from non-linear loads, sudden load changes, network events and the electrical structure of the facility itself. Poor power quality can cause overheating in equipment, nuisance tripping, energy losses, shorter equipment life and interruptions to production continuity. At EPKOM we use power quality analyzers to measure and monitor LV and MV systems, recording harmonics, voltage events and the other power quality parameters. We evaluate the resulting data against the relevant standards, such as EN 50160, IEC 61000 and IEEE 519, according to the measurement point and the scope of the application. Following measurement and analysis, we apply active and passive harmonic filters, SVG systems, compensation solutions and power quality monitoring systems according to the needs of the facility, helping the electrical infrastructure run more safely, efficiently and stably.
- Energy Monitoring SystemsEnergy monitoring systems measure and analyse electricity consumption continuously, at facility, feeder, department or machine level. Alongside electricity, other energy sources such as water, natural gas and compressed air can be tracked through the same system. Data from Janitza energy analyzers is collected centrally in the GridVis software, where consumption trends, load profiles and energy performance indicators can be followed. Automatic reporting and alarm functions make abnormal consumption and energy losses quick to identify. Energy monitoring systems help to allocate energy costs correctly, to identify inefficient points of consumption and to improve energy performance continuously. They also support ISO 50001 energy management processes and make it possible to track energy performance indicators such as PUE in data centers.
Technical Specifications
UMG 96-PA-MID+
| Voltage inputs | MID-rated 3×57.7/100V … 3×289/500V (same base platform as UMG 96-PA) |
|---|---|
| Current inputs | 1A/5A CT, optional 100V VT; MID range 0.002–6A |
| Accuracy class | 0.2S/0.5 non-MID; Accuracy Class B for the MID-certified metrology function |
| Frequency | 45–65 Hz (ref. 50 Hz) |
| Communication protocols | RS485 (Modbus RTU); optional Ethernet module adds Modbus TCP/IP + Gateway |
| Memory / data logging | 8 MB |
| Installation type | Panel mount, 96×96 mm cut-out, same housing as UMG 96-PA |
| Certifications / standards | 600V CAT III / 300V CAT IV; MID Electromagnetic Class E2, Mechanical Class M1; UL listed |
| Power supply | 90–277 V AC / 90–250 V DC |
Technical values are taken from the manufacturer's published documentation. Confirm against the current datasheet before ordering.
Downloads
Datasheets, manuals and technical documentation are available from the manufacturer's document centre, or on request from us.
Get in Touch
Contact us about this product
Let us work out the right model for your application. Share your single-line diagram or measurement data and our technical team will review it.