Skip to content
ProData 2 · Janitza Electronics GmbH
Janitza Electronics GmbHData Logger

ProData 2

Data logger and Modbus gateway

ProData 2 is Janitza's stand-alone data logger for collecting consumption and process data at the measurement points and passing it on to the energy monitoring software. Its 15 digital inputs count pulses from electricity, water, gas and heat meters, its temperature input records a PT100/PT1000/KTY sensor, and its built-in Modbus gateway brings RS485 Modbus RTU devices onto the Ethernet network. Data is kept in its own flash memory, so consumption and power quality data can be held centrally over the long term and analysed in GridVis.

Technical Specifications

ProData 2

Technical Specifications · ProData 2
Item number5224011
Power supply20–250 V AC (45–65 Hz) / 20–300 V DC; max. 4 VA / 2 W
Digital inputs15, 20–30 V DC; S0 pulse input to DIN EN 62053-31, max. 25 Hz
Digital outputs3 semiconductor relays, max. 60 V DC / 50 mA; pulse output max. 20 Hz
Temperature input1 × 3-wire; PT100, PT1000, KTY83, KTY84
Communication protocolsRS485 Modbus RTU (9.6–115.2 kbps); Ethernet RJ45: Modbus TCP (port 502), Modbus gateway, DHCP, NTP
Memory / data logging32 MB flash
Dimensions107.5 × 90 × 46 mm; approx. 200 g
Installation type35 mm DIN rail
ProtectionIP20 (EN 60529), protection class II
Operating temperature-40 … +55 °C